3. Description

3.5 Description of the K3 control panel

1. General ON (1) / OFF (0) switch

2. Burner alarm indicator

This indicator lights up when the burner is on safety (faulty).

3. Switch AUTO/

!

/TEST-STB

Position AUTO: This position enables automatic operation of the
installation in accordance with DIEMATIC-m 3 regulation
controls.
Position

!

: The boiler no longer takes orders from the

DIEMATIC-m 3 regulation into account. The boiler is regulated
by the boiler thermostat(s).
Position TEST-STB: Temporary action to test the safety
thermostat

4. Safety thermostat with manual reset

Set at 110° C

5. Timed circuit breaker (10 A) with delayed action and manual

reset

6. Pump shutdown switch

7. Boiler thermostat (30 to 90 °C)

A factory-set stop limits the maximum temperature to 75 °C. The
stop may be moved if necessary.

Z

See "Moving the thermostat stop".

8. Boiler thermometer. Boiler temperature display.

9. Switch for selecting the number of burner stages

10. Connector for the programming tool