3 control panel diematic-m3 – DE DIETRICH GTU C 330 User Manual

Page 19

Advertising
background image

19

24/11/08 - 300017846-001-B

GTU C 330

8. Troubleshooting

8.2.3

Control panel DIEMATIC-m3

Message

Probable causes

Action

SHOW REM. CTRL

The message SHOW REM.CTRL indicates the
presence of an override on a remote control.

To cancel the overrides on all remote controls, press the AUTO key for 5
seconds.

REVISION

Boiler service required.

Advise the installer.

DISGAS

When connecting voltage, if the hot water tank
temperature is below 25 ºC, the boiler carries out a
domestic water exchanger purge cycle.

Wait 1 minute.

AUX1.SENS.FAIL
AUX2.SENS.FAIL

UNIV.SENS.FAIL

DHW 2 S. FAIL

The sensor circuit has been broken or short
circuited.

Advise the installer.

BOILER S.FAIL.

The sensor circuit has been broken or short

circuited.

If the boiler sensor fails, the burner is controlled by the boiler thermostat and
the heating and DHW circuits operate normally.
Advise the installer.

OUTSI. S.FAIL.

The sensor circuit has been broken or short

circuited.

The boiler setting is equal to BOILER MAX. but can be limited by the boiler
thermostat to a lower value.
- The valve setting is no longer ensured but monitoring the maximum
temperature of the circuit after the valve is ensured.
- Valves may be manually operated.
- Reheating the domestic hot water remains ensured.
Advise the installer.

DHW S. FAILURE

The sensor circuit has been broken or short

circuited.

To ensure domestic hot water production, set the switch AUTO/

!

/TEST-

STB to

!

.

Advise the installer.

OUTL S.A FAIL.
OUTL S.B FAIL.
OUTL S.C FAIL.

The sensor circuit has been broken or short

circuited.

The circuit concerned goes from automatic to manual mode: The pump
operates.
Advise the installer.

ROOM S.A FAIL.
ROOM S.B FAIL.
ROOM S.C FAIL.

The sensor circuit has been broken or short

circuited.

The circuit concerned operates without any influence from the room sensor.
Advise the installer.

SMOKE S. FAIL.

The sensor circuit has been broken or short

circuited.

This failure has no impact on the operating modes.
Advise the installer.

SWIM.P.A S.FAIL

SWIM.P.B. S.FAIL
SWIM.P.C. S.FAIL

The sensor circuit has been broken or short

circuited.

Pool reheating is independent of its temperature.
Advise the installer.

SOLAR S. FAIL

The sensor circuit has been broken or short

circuited.

Reheating domestic hot water using the solar panel is no longer ensured.
Advise the installer.

ST.TANK S.FAIL

The sensor circuit has been broken or short

circuited.

The hot water storage tank reheating operation is no longer assured.
Advise the installer.

TA-S SHORT-CIR

The Titan Active System® is short-circuited.

Domestic hot water production is shut down and can be restarted using key



. The tank is no longer protected.

Advise the installer.

TA-S DISCONNEC

The Titan Active System® is on an open circuit.

Domestic hot water production is shut down and can be restarted using key



. The tank is no longer protected.

Advise the installer.

TA-S FAILURE

Internal problem.

Switch off the current.
Advise the installer.

Advertising