background image

8

GTU C 330

24/11/08 - 300017846-001-B

3. Description

3.4 Description of the B3 control panel

1. General ON (1) / OFF (0) switch

2. Alarm indicator

This indicator lights up when the burner is on safety (faulty).

3. Switch TEST-STB/

.

/

%

Position

.

: DHW + Heating

Position

%

: DHW

Position TEST-STB: Temporary action to test the safety
thermostat

4. Safety thermostat with manual reset

Set at 110° C

5. Timed circuit breaker (10 A) with delayed action and manual

reset

6. Pump shutdown switch

7. Electronic thermostat

Set the boiler temperature between 30° C and 90° C using
manual setting.

8. Indicator lights up

Boiler temperature display

9. Location for flue gas thermometer (optional)

10. Switch for selecting the number of burner stages

„

When preparing domestic hot water

11. Electronic thermostat

Regulating the storage temperature of domestic hot water between
10° C and 80° C.
12. Indicator lights up

Domestic hot water display



After switching on, the system performs an automatic purge of
the accumulator interchanger for one minute by intermittently
operating the domestic load pump and the heating pump. This
purge sequence is deactivated if the temperature in the
accumulator is above 25º C.

13. Location for hour run meter (Option)