Installation and operation manual, Figure 1-9b cam setting for alarm signal – Brooks Instrument MT3809G User Manual
Page 28
Advertising
1-22
Installation and Operation Manual
X-VA-MT3809G-MT3810G-eng
Part Number: 541B182AAG
September, 2013
Models MT3809G & MT3810G
Section 1 Introduction
Figure 1-9A Power Supply vs. Maximum Load Resistance
Note: load resistance should also include I.S. barrier resistance. When using HART
communicator the minimum load resistance is 250 ohms.
Figure 1-9B Cam Setting for Alarm Signal
Loop Voltage vs. Load Resistance
600
650
700
750
800
850
900
950
1000
1050
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
Loop Voltage
Load
Resistance
Loop Resistance (maximum ohms) = 30 X voltage + 16