Assembly

7.2.

attachment to a proportional valve

Attach the process controller Type 8611 to a proportional valve as described below.

→

Loosen the 4 screws at the front of the process controller.

NOTe!

Be careful when opening the process controller so as not to damage the internal cabling.

• Remove the cover carefully from the housing without jerks.

→

Remove the cover carefully from the housing.

→

Place the supplied flat seal over the contact tabs.

→

Attach the housing of the process controller on the contact tabs and fasten with the valve screw.

→

Check the correct position of the profile gasket at the housing of the process controller.

→

Place cover on the housing of the process controller and fasten with 4 screws.

If necessary, the cover can also be mounted in a position rotated by 90 ° to the left or the right.

Proportional valve

Contact tabs

Profile gasket

Valve screw

Flat seal

Housing of the process controller

Cover of the

process controller

4 screws for fastening the cover

Figure 5:

Attachment of the process controller to a proportional valve