Burkert Type 8611 User Manual
Page 54

54
FunctionsoftheConfigurationLevel
Bleed valve
(NO operating principle = Normally open / opened with no current)
Aeration valve
(NC operating principle = Normally closed / closed with no current)
Figure 35:
Control block 8810 for control of the process valve
If control valves other than those of Type 8810 are used, the opening time specified in the data sheet for "
TMN1"
or the closing time for "
TMN2" can be used.
To ensure that the process valve moves automatically into closed position in the event of a power failure, observe
the operating principle of the control valves:
• Control valve for aeration
=
NC operating principle / Normally closed ( closed with no current)
• Control valve for deaeration
=
NO operating principle / Normally Open (opened with no current)