FunctionsoftheConfigurationLevel

12.13.1.

KP1, KP2 - setting the proportional coefficient

(proportional gain)

Depending on the actuating element selected in the

MODE menu (see chapter 12.3), the influence of the propor-

tional coefficient varies. It serves as proportional gain [K

p

] either for opening or for closing the actuating element.

calculation of the proportional gain [K

p

]:.

Calculation for continuous control (

MODE = SCV, 4 – 20 or 0 – 10):

The proportional gain is calculated by dividing the value for the manipulated variable change [∆%] by the value for
the process value change [∆PV].

∆%
∆PV

Manipulated variable change
Process value change

K

p

=

Depending on the selected actuating element in the

MODE menu the manipulated variable is scaled as follow:

MODE = SCV

0 % = Pulse duty factor 0 %

100 % = Pulse duty factor 100 % (relatively to PWM-

frequency)

MODE = 0 - 10

0 % = Manipulated variable 0 V

100 % = Manuipulated variable 10 V

MODE = 4 - 20

0 % = Manipulated variable 4 mA 100 % = Manipulated variable 20 mA

MODE = 2P - T

0 % = Valve closed

100 % = Valve (VLV1) open in relatio to time T

reg

(T

reg

= 100 %)

MODE = 3P - T

0 % = Valve 1 closed

100 % = Valve 1 (VLV1) in relatio to time T

reg

(T

reg

= 100 %)

0 % = Valve 2 closed

-100 % = Valve 2 (VLV2) in relatio to time T

reg

(T

reg

= 100 %)

MODE = PCV

0 % = Valve 1 closed

100 % = Valve 1 (VLV1) in relatio to time T

reg

(T

reg

= 100 %)

0 % = Valve 2 closed

-100 % = Valve 2 (VLV2) in relatio to time T

reg

(T

reg

= 100 %)

Speciality: The controller operates as a discontinous 2-state controller or 3-state controller if in the

MODE menu

as actuating element

2P - T or 3P - T is selected and the proportional gain K

p

is set to 9999 (independent from

decimal place). The parameters T

reg

and T

n

have no influence to the control..

The influence of the proportional value on the actuating element and the calculation of the proportional gain:

actuating
element
(selection in
MODE =)

influence proportional
coefficient

calculation of the
proportional gain
[K

p

]

value range

SCV
4 – 20
0 – 10

Proportional gain K

p1

for

opening and closing the
actuating element

∆%
∆PV

K

p1

=

0.001 – 9999
Changing the decimal places

→

Press the ENTER key to select KP1 or KP2.

→

Use the arrow key to move to the left until the
decimal place flashes.

→

Now use the up arrow key to position the
decimal place at the correct place and
confirm with ENTER.

PCV
2P – T
3P – T

Proportional gain K

p1

for

opening the actuating
element

∆%
∆PV

K

p1

=

PCV
3P – T

Proportional gain K

p2

for closing the actuating
element

∆%
∆PV

K

p2

=

Table 27:

KP1, KP2 - Proportional gain