To series 2103 and 23xx – Burkert Type 8694 User Manual

Page 12

Advertising
background image

12

Installation

7.2. Installing the positioner on process

valves belonging to series 2103 and
23xx

Procedure:

When the positioner is being installed, the collets of the pilot
air ports must not be fitted to the actuator.

Align the puck holder and the positioner until
1. the puck holder can be inserted into the guide rail of the

positioner (see “Fig. 4”) and

2. the supports of the positioner can be inserted into the pilot

air ports of the actuator (see also “Fig. 5”).

NOTE!

Damaged printed circuit board or malfunction!
• Ensure that the puck holder is situated flat on the guide rail.

Guide rail

Puck holder

Fig. 4:

Aligning the puck holder

Push the positioner, without turning it, onto the actuator until no
gap is visible on the form seal.

NOTE!

Too high torque when screwing in the fastening screw does
not ensure protection class IP65 / IP67!
• The fastening screws may be tightened to a maximum torque of

0.5 Nm only.

Attach the positioner to the actuator using the two side fastening
screws. In doing so, tighten the screws only hand-tight (max.
torque: 0.5 Nm).

Supports

Pilot air

ports

Fastening

screws

max. 0.5 Nm

Actuator

Fig. 5:

Aligning the puck holder, series 2103, 2300 and 2301

english

Type 8694

Advertising