Start-up

10.3.3. Function of the DIP switches

DIP
switches

Function

ON

DIP

1 2 3 4

1

ON

Reversal of the effective direction of the set-point
value (set-point value 20 – 4 mA corresponds to
position 0 – 100 %), descending (

DIR.CMD)

OFF

Normal effective direction of the set-point value
(set-point value 4 – 20 mA corresponds to position
0 – 100 %), ascending

2

ON

Sealing function active. The valve completely closes
below 2 %

12)

and opens above 98 % of the set-point

value (

CUTOFF)

OFF

No sealing function

3

ON

Correction characteristic for adjustment of the oper-
ating characteristic (linearization of the process char-
acteristic

CHARACT)

12)

OFF

Linear characteristic

4

ON

Operating status MANUAL (MANU)

OFF

Operating status AUTOMATIC (AUTO)

Tab. 10: DIP switches

12)

Can be changed via communications software.

10.3.4. Display of the LEDs

1 2 3 4

ON DIP

Communications
interface
LED 1
LED 2
DIP switches

Key 1

Key 2

Fig. 17: Display of the LEDs

LED 1
(green / red)

Display of
AUTO, MANU,

X.TUNE and FAULT

LED 2
(green / yellow)

Display of state of actuator