English, 6factory setting – Burkert Type TAT002 User Manual
Page 19

0911 - 17
english
6
FACTORY SETTING
PA
1
Description
Range
Default
PE
2
SET
Set-value
LS1 + US1
0
Pr1
HY1
Switch hysterisis 1
dependent on measurement
range
-1
Pr1
LS1
Lowest set-value 1
Lower measurement range +
SET1
min
Pr2
US1
Largest set-value 1
Upper measurement range +
SET1
max
Pr2
S1C
Control effect Output 1
in = inverse; dir = direct
in
Pr2
Ac
Delay time for the relay
0...250 sec
0
Pr2
on
Minimum switch-on time
for a relay
0...250 sec
0
Pr2
ono
Minimum waiting time
between two consecutive
activations of the same
load
0...120 min
0
Pr2
ALC
Alarm limits are absolute
values or related to the
set-value
rE = relative; Ab = absolute
rE
Pr2
ALL
Lower Alarm Limit
(ALC = rE; ALC = Ab)
dependent on measurement
range
10
Pr2
ALU
Upper Alarm Limit
(ALC = rE; ALC = Ab)
dependent on measurement
range
10
Pr2
ALH
Switch hysterisis for
temperature alarms
dependent on measurement
range
2
Pr2
ALd
Alarm delay time during
the operation
0...999 min
15
Pr2
dAO
Alarm delay time after
commissioning
0...23.5 h
1.3
Pr2
So1
Output 1 for sensor error
oFF = open; on = closed
oFF
Pr2
tbA
Alarm relay can be
acknowledged
no; yES
yES
Pr2
AS
Polarity of the Alarm
relay
CL...oP
oP
Pr2
LCI
3
Lower analog display
value
depending on sensor
var.
Pr2
1
Parameter
2
Programming level
3
Only for devices with voltage and current input