English, 8repair work 8.1 faults – Burkert Type TAT002 User Manual
Page 21

0911 - 19
english
8
REPAIR WORK
8.1
Faults
ERROR MESSAGES
Message
Cause
Effect
PFo
Sensor defective or not
connected
Alarm relay ON; control circuit
according to So1
PFc
Sensor short-circuit
Alarm relay ON; control circuit
according to So1
HA
High temperature alarm
Alarm relay ON; outputs remain
unchanged
LA
Low temperature alarm
Alarm relay ON; outputs remain
unchanged
EAL
Digital input alarm
Outputs remain unchanged
BAL
Serious digital alarm
All control outputs deactivated
STATUS OF THE ALARM RELAY
Device status
AS = CL
AS = OP
Device without power
4 - 6 closed
4 - 6 closed
Normal operation
4 - 6 closed
4 - 6 open
Alarm situation during
operation
4 - 6 open
4 - 6 closed
ACKNOWEDGING ERRORS VIA THE KEYBOARD
Press any button.
The Alarm message remains on the display as long as the alarm conditions
are present. The device then switches to normal operation.
AUTOMATIC ACKNOWLEDGEMENT OF THE ERROR
•
Message
PFo and PFc - Room sensor error
After approx. 30 seconds or once the error has been cleared, the
message will be acknowledged automatically. Check the connections
before any replacement of the sensor.
•
Messages
HA/LA - High/Low temperature alarm
After a few seconds or once the error has been cleared, the message will
be acknowledged automatically.
•
External alarms
EAL and BAL are acknowledged after deactivation of the
digital input.