English, 3 kfac - setting the k factor – Burkert Type 8623 User Manual
Page 26

24 - 8623-2 Standard
english
The K factor enables the output frequency of the flow rate sensor to be normalized
to the flow rate:
Q
flow rate
k
k factor
f
output frequency of the flow rate sensor
The K factor states the number of pulses per unit volume:
The K factor should be taken from the data sheet of the flow rate sensor used or
the fitting used. The volume base of the K factor determines the unit of flow rate,
e.g:
resulting in a flow rate in litre per time base.
Q
1
k
f
k
Impuls
V
k
46,60
Impulse
Liter
6.6.3
KFAC - setting the K factor
ATTENTION!
The K factor must be set to agree with the unit chosen.
The display shows values in the range 0 to 6552. If it is
attempted to set a higher value, the display will jump
automatically to 0 and a value must be entered within the range
(factory setting: 46.60).
increase digit
next digit
2 s
set decimal
point
Fig.: setting the K factor