English, 5 ampl - setting the amplification k – Burkert Type 8623 User Manual
Page 31
Advertising

8623-2-Standard - 29
english
increase digit
next digit
2 s
set decimal point
6.6.5
AMPL - setting the amplification K
p
Î
Select the amplification factor K
P
in a range from 0.00 to 10.00
o
/
oo
/Hz
(factory setting: 1.00). If it is attempted to set a higher value, the display will
jump automatically to 0 and a value must be entered within the range.
Setting aid:
•
If excessive overshoot occurs at the value of K
P
set or the control
becomes unstable, you should decrease K
P
.
•
On the other hand, unsatisfactory control dynamics may be improved by
raising K
P
as long as the abovementioned instability does not occur.
Fig.: Setting the amplification K