AS Interface - Design

Calculation examples:

example 1:
3 valves are activated simultaneously, one position is reported (state for 200 ms):

P

Slave

=

P

El

+ 1 x P

Valve-On

+ 2 x P

Valve

+ 1 x P

LED

4.5 W =

1.0 W

+ 1 x 0.9 W

+ 2 x 0.8 W

+ 1 x 1.0 W

or

I

Slave

=

I

El

+ 1 x I

Valve-On

+ 2 x I

Valve

+ 1 x I

LED

148 mA =

33 mA

+ 1 x 30 mA

+ 2 x 26 mA

+ 1 x 33 mA

example 2:
3 valves have been activated simultaneously, one position is reported (persistent state):

P

Slave

=

P

El

+ 3 x P

Valve

+ 1 x P

LED

4.4 W =

1.0 W

+ 3 x 0.8 W

+ 1 x 1.0 W

or

I

Slave

=

I

El

+ 3 x I

Valve

+ 1 x I

LED

144 mA =

33 mA

+ 3 x 26 mA

+ 1 x 33 mA

When using an external initiator, its power requirement should be added.

safety instructions

11.6.

Danger!

danger of explosion in explosive atmosphere (only in the event of a fault as zone 2)!

Opening the hood or the housing in an explosive atmosphere is only allowed in the isolated state!

•

Warning!

risk of injury due to electrical shock!

Before reaching into the system (except for the Teach-In procedure in a non-explosive atmosphere) switch off

•

the power supply and secure it to prevent restarting!

Observe applicable accident prevention and safety regulations for electrical equipment!

•

risk of injury from improper installation!

Installation may be carried out by authorized technicians only and with the appropriate tools!

•

risk of injury from unintentional activation of the system and an uncontrolled restart!

Secure system from unintentional activation.

•

Following installation, ensure a controlled restart.

•