Maintenance, Cleaning, Malfunctions – Burkert Type 8681 User Manual

Page 79: Cleaning 18.4, Malfunctions 18.5

Advertising
background image

79

Maintenance, Troubleshooting

18.3. Maintenance

When used properly, the Control Head Type 8681 operates maintenance and trouble-free.

For service work, we offer spare part sets for certain components or modules (see chapter entitled "

20. Spare

Parts"). Repairs to the control head for use in explosive atmosphere, however, are only allowed by the
manufacturer.

If service function is active (see chapter

6.6. Factory Settings in the Firmware) a maintenance prompt is issued -

signaled by a "blinking pattern" in the fault color (1 s ON, 3 s OFF) - see chapter

16.2. Blinking Pattern & Fault

Signaling.

Cleaning

18.4.

note!

aggressive cleaning agents may damage the material!

In the explosion-risk area, only wipe the control head with a damp or anti-static cloth to avoid electro-static

charges.

The customary cleaning agents and foam cleaners can be used to clean the outside. We recommend

checking that the cleaning agents are compatible with the housing materials and seals before using the
cleaning agent.

Clean the control head and rinse it thoroughly with clean water to safeguard against the formation of deposits

in grooves and recesses.

If cleaning agent is not rinsed off carefully, its concentration may considerably exceed the concentration for
use once the water has evaporated. The chemical effect will thus be several times stronger!

Observe the specifications of the manufacturer and the recommendations for use of the cleaning agent
manufacturer!

Malfunctions

18.5.

In the event of any malfunctions in spite of a correct installation, proceed according to the fault analysis described
in the table below:

fault description

possible cause of the fault

troubleshooting

No feedback signal

Position of the position measuring
system (Teach-In) not appropriate
for the spindle position

Perform or repeat the Teach-In process
(see chapter

15.1. Setting the Position

Measuring System (Teach-In))

Setting of the external initiators
incorrect

Set the external initiator according to the
respective operating instructions.

No or faulty associated feedback
signals or external initiator

Set the connections according to the
pin and plug configurations described
in these operating instructions (for the
respective voltage and communication
variant).

Target is not mounted on the
process valve's spindle or target
faulty

Check the target for correct mounting
and condition (see chapter (

6.5. Position

Measuring System Data)).

english