Fig. 46 – Burkert Type 8045 User Manual

Page 52

Advertising
background image

48

Operatingandfunctions

The preset flow rate is ignored if there is a running check for the correct behaviour of the outputs (see
chap. “8.7.3”).

This function makes it possible, like the Hold mode, to freeze the flow rate maesure, but to a preset value set by
the user.

When the digital input is activated:

• the device status LED flashes.

• the current transmitted on the 4-20 mA is frozen to the preset value of the flow rate.

• the displayed flow rate is frozen to the preset value of the flow rate.

• each transistor or relay output behaves depending on the preset flow rate.

• the totalizers do not increment any more.

• the preset flow rate is active until the digital input switches again.

iNPUt

Di1

sEt FLOw

REtURN

iNV YEs

iNV NO

0......9

→

Choose "INV. NO" to trigger the input on the leading
edge.

→

Choose "INV. NO" to trigger the input on the trailing
edge.

→

Confirm

sF= 0.000

→

Enter the flow rate value, in the unit chosen in the
"UNIT".parameter.

→

Confirm

Fig. 46:

Configuration of the digital input to trigger the status of the outputs depending on a preset flow rate

English

Type 8045