Wire The Controls

Two pigtail wires are provided inside the
electrical compartment of the humidifier. This
“AB” to “AB” circuit is the low-voltage control
for the humidistat and air pressure switch.
The humidifier will run when the AB-AB
Circuit is completed.

24 volt A.C. to power the E1 Humidistat may
be pulled from the “G” and “GND” terminals.

The AB-AB circuit is completed through the
12500 Pressure Switch (“NO”, “C” terminals)
and the E1 Humidistat (“OUT” terminals).

If it is desired for the humidifier to activate the
heating fan during a call for humidity use the
second wiring scheme below.

terminal

function

electrical specifications

+VR
SET

Enabling jumper

external N/O contact; R

max

=50 ; V

max

=10Vdc; I

max

=1mAdc

AB
AB

Input from humidistat remote

enabling input

external N/O contact; R

max

=50 ; V

max

=24Vdc; I

max

=10mAdc

G

GND

24V AC power supply for E1

Humidistat and relay

Output V

max

=24Vac; LOAD

max

=500mA ac