Alarms, troubleshooting – GeneralAire DS20 Elite Steam User Manual

Page 16

Advertising
background image

16

9. Alarms, Troubleshooting

Alarms are indicated on the front display panel by a sequence of flashes of the red alarm LED. In the
event of more than one alarm, these are indicated in sequence. Even if no longer active, the
alarm status continues to be displayed by the flashing of the LED and the operation of the
humidifier is stopped while the alarm is still present. To clear the inactive alarms, the humidifier
must be turned off, and then on again. Active alarms cannot be reset by restarting the
machine.

LED flash modes
: slow flashes - 1 flash every 2 seconds; quick flashes - 2 flashes per second;
the signals are repeated continuously, and the LED stays off for 3 seconds between one signal
and the next.

Display

Causes

Solution

Action

2 quick flashes

red LED

Current overload in
the electrodes;
probable fault in the
electrodes or water
temporarily too
conductive
(especially on re-
start after a brief
pause)

Drain part of the water and re-start

Total
shut-

down

3 quick flashes

red LED

High level is
indicated but no
amperage draw is
present

With the machine off and disconnected from the main power
supply, check the condition of the cylinder and the electrical
connections

Total
shut-

down

2 slow flashes

red LED

End of cylinder life

Turn the machine off and replace the cylinder

Signal

only

3 slow flashes

red LED

No water

Check that the supply water tubing to the humidifier and the
internal tubing are not blocked or bent and that there is proper
pressure;
Check the operation of the supply valve;
Check that the steam outlet does not have excessive back-
pressure, preventing the flow of water into the cylinder by
gravity;
Check that the steam outlet hose is not choked or that there
are pockets of condensate

Total
shut-

down

4 slow flashes

red LED

Excessive reduction
in steam output

End cylinder life or alternatively water with excessive foam

Total
shut-

down

5 slow flashes

red LED

Drain malfunction

Check the water drain circuits and the correct operation of the
drain valve

Total
shut-

down

6 slow flashes

or 3 quick

flashes

red LED

Internal memory
error

Contact the Dealer

Total
shut-

down

9 slow flashes

Cylinder full with
humidifier off-duty

Turn off the machine and check whether the full electrovalve
leaks or there is some condensate entering the cylinder from
the steam distributor

Total

shutdown