Once started, the LEDs on the control panel at the bottom
front of the humidifier will glow to indicate operation



LED Position

Means

Green Left

Power

on

Yellow Center

Humidification in progress

Red

Right

Signals and alarms. These are indicated by specific flashes.

Sequence Of LED Flashes On Start-Up

On start-up, the humidifier performs a sequence of flashes of the LEDs on the front panel. Please
note that the green LED remains on for the entire time the machine is on, irrespective of the
operating status. The sequence consists of the following operations:
1. Power connected: the yellow and red LEDs remain off for 1 second;
2. Initialization: the yellow and red LEDs flash a number of times to indicate the version of the

program that the board is configured with; this occurs once each time the machine is started;

a. First the yellow LED - the number of flashes indicates the tens (0=no flash);
b. Then the red LED - the number of flashes indicates the units (0=no flash); example:

version 1.1: 1 flash of the yellow LED, then 1 flash of the red LED;

c. Once the sequence of flashes corresponding to the unit is completed, the LEDs remain

off for 3 seconds, followed by the start of operation.

3. Operation: the humidifier starts operation; the yellow LED indicates that production is in
progress, as shown by the following table:

Yellow LED

Production

Off 0%
1 flash

1% to 19%

2 flashes

20% to 29%

3 flashes

30% to 39%

… …
9 flashes

90% to 99%

Always on

100%


Remark:
the transient production is signalled by short flashes: on and off twice in 1 second; each
sequence of flashes repeats continuously and, between one sequence and the next one, the yellow
LED stays off for 3 seconds.

Indication Of An Alarm

When an alarm occurs, the red LED starts to flash. The number of the flashes followed by a pause
indicates specific alarms. See ALARMS, TROUBLESHOOTING.

Shut-Down

During seasonal shut-down or shut-down for maintenance, the humidifier should be placed out-of-
service.