12. Technical Specifications

Model

DS-20

Duct Kit

RS-20

Fan Kit

rated power supply voltage (Vac)

230

steam connection (

φ inches)

7/8”

steam outlet pressure limits (inches w.c.)

0 to 8” w.c.

operating conditions

temperature 34 to 104

°F,

humidity 10 to 60% RH

storage conditions

temperature 14 to 158

°F,

humidity 5 to 95% RH

noncondensing

index of protection

IP20

auxiliary voltage / frequency (V - Hz)

24 Vac, 50/60 Hz

maximum auxiliary power (VA)

25 VA

instant steam production (1) (lbs/hr)

7 lbs/hr

7 lbs/hr

power consumed at rated voltage (kW)

2.40 kW

2.40 kW

duct steam nozzle

High

temperature

plastic

N/A

steam hose

High temperature EPDM

water pressure

15 to 150 psi

water conductivity

125 to 1250 micromhos

room blower unit air volume

N/A

100 CFM

room blower unit power consumption

N/A

30 Watts

room blower unit noise level

N/A

50 dBA

(1) the average steam production is affected by factors such as: ambient temperature, water quality, steam distribution system

Dimensions and weights

A 14-1/8”

B 10-1/4”

C 24-3/8”

packaged 40

lbs.

B

A

C

empty 29.7

lbs.

Wet *

36.4 lbs.

*: in normal operating conditions,
filled with water

RS-20 (due to
blower)

add 9” high
add 10 lbs.