Page 14
Elite Steam +030222075 Rev. 3.5 – July 2012
14
20%
5%
20%
20%
5%
1,5 m (5 FT max.)
3 m ( 10 FT max.)
20%
0,
9 m
(
3
FT
m
ax.
)
1,5 m (5 FT max.)
1,5 m (5 FT max.)
YES
NO
P - TRAP
NOTE: HEIGHT OF TRAPS MUST BE GREATER
THAN THE DUCT STATIC PRESSURE
NOTES:
• SLOPE PIPING UP IN DIRECTION OF STEAM FLOW AT 20% OR GREATER, WHICH MEANS 65,5mm x 305mm (2 1/ 2” PER FOOT);
• SLOPE PIPING DOWN IN THE DIRECTION OF STEAM FLOW AT 5% OR GREATER, WHICH MEANS 20mm x 305mm (3 /4” PER FOOT);
• MAX. LENGTH OF RUBBERSTEAM HOSE IS 3 m ( 10 FT).
• HEIGHT OF P-TRAPS MUST BE GREATER THAN T
HE DUCT STATIC PRESSURE.
TYPICAL INSTALLATION
WHEN UNIT IS ABOVE
THE DISTRIBUTOR PIPE
GENTLEBEND
OBSTRUCTION
SUPPORTED STEAM HOSE
AND/ ORCOPPERPIPE
DRAINS
IF NO TRAP
WITH TRAP
DRAINS
IF NO SLOPE
NO SLOPE
NO SLOPE
KINKED
NO TRAP
UNDRAINED
ELBOW
UNDRAINED
ELBOW
NO DISTRIBUTION
PIPE DRAIN
SAG
Fig. 3.m
IMPORTANT: Maximum length of rubber steam hose is 4m (12 feet.). Insulated copper tubing may be up to 6m(20feet) in
length. In all cases, minimize sharp bends and elbows. Use 2 - 45° elbows instead o f 90°s.
Hose inner diameter = 7/8” ( 22 mm); Hose outer diameter = 1-1/4” (30 mm).
3.4.4 Remote Mount Blower
Remote Mount Blowers, are used to distribute the steam directly into the room. The drawings show the
minimum recommended
distances to avoid the flow of humidified air from coming into direct contact with persons, lights, electrical appliances, and surfaces
before the steam has been totally absorbed by the environment. For further details on the assembly, the electrical connections and
the use of a Remote Mount Blower, please refer to the specific instruction manual.
20%
A
C
B
D
Millimeters Inch
A
150 mm
6”
B 1800 mm
72”
C
600 mm
24”
D 2100 mm
84”
Tab. 3.g
Fig. 3.n