Elite Steam +030222075 Rev. 3.5 – July 2012

14

20%

5%

20%

20%

5%

1,5 m (5 FT max.)

3 m ( 10 FT max.)

20%

0,

9 m

(

3

FT

m

ax.

)

1,5 m (5 FT max.)

1,5 m (5 FT max.)

YES

NO

P - TRAP

NOTE: HEIGHT OF TRAPS MUST BE GREATER

THAN THE DUCT STATIC PRESSURE

NOTES:

• SLOPE PIPING UP IN DIRECTION OF STEAM FLOW AT 20% OR GREATER, WHICH MEANS 65,5mm x 305mm (2 1/ 2” PER FOOT);

• SLOPE PIPING DOWN IN THE DIRECTION OF STEAM FLOW AT 5% OR GREATER, WHICH MEANS 20mm x 305mm (3 /4” PER FOOT);

• MAX. LENGTH OF RUBBERSTEAM HOSE IS 3 m ( 10 FT).

• HEIGHT OF P-TRAPS MUST BE GREATER THAN T

HE DUCT STATIC PRESSURE.

TYPICAL INSTALLATION

WHEN UNIT IS ABOVE

THE DISTRIBUTOR PIPE

GENTLEBEND

OBSTRUCTION

SUPPORTED STEAM HOSE

AND/ ORCOPPERPIPE

DRAINS

IF NO TRAP

WITH TRAP

DRAINS

IF NO SLOPE

NO SLOPE

NO SLOPE

KINKED

NO TRAP

UNDRAINED

ELBOW

UNDRAINED

ELBOW

NO DISTRIBUTION

PIPE DRAIN

SAG

Fig. 3.m

IMPORTANT: Maximum length of rubber steam hose is 4m (12 feet.). Insulated copper tubing may be up to 6m(20feet) in

length. In all cases, minimize sharp bends and elbows. Use 2 - 45° elbows instead o f 90°s.

Hose inner diameter = 7/8” ( 22 mm); Hose outer diameter = 1-1/4” (30 mm).

3.4.4 Remote Mount Blower

Remote Mount Blowers, are used to distribute the steam directly into the room. The drawings show the

minimum recommended

distances to avoid the flow of humidified air from coming into direct contact with persons, lights, electrical appliances, and surfaces

before the steam has been totally absorbed by the environment. For further details on the assembly, the electrical connections and

the use of a Remote Mount Blower, please refer to the specific instruction manual.

20%

A

C

B

D

Millimeters Inch

A

150 mm

6”

B 1800 mm

72”

C

600 mm

24”

D 2100 mm

84”

Tab. 3.g

Fig. 3.n