Elite Steam +030222075 Rev. 3.5 – Aug. 2013

15

3.5 Power wiring

Check that the power supply voltage to be connected matches the value indicated on

the rating plate inside the electrical panel.

Insert the power and ground connection cables into the electrical panel compartment

using the strain reliefs supplied, and connect to the terminals. An external fused

disconnect must be installed. See Fig. 3.o

All wiring must be in accordance with local, state and national electric codes.

NOTE: to avoid unwanted interference, the power cables should be kept separate

from any control wiring.

NOTE: Tolerance allowed on main voltage =-15% to +10%.

Connect power wires to the power terminal block located at the bottom left of the

control module, polarity does not matter. See Fig. 3.p

Connect the ground wire to the unit’s chassis ground, located just behind the power

wiring terminal block. See Fig. 3.q

Model

Power supply

(single phase)

Steam Output

(lbs/hr)

Steam Output

(kg/h)

POWER

(kW)

CURRENT

(A)

EXTERNAL

POWER WIRES

EXTERNAL FUSE (A)

OR BRAKER

DS15

110Vac 50/60Hz

5.5

2.5

1

.80

16

.40

AWG10

25

RS15

110Vac 50/60Hz

5.5

2.5

1.80

16.40

AWG10

25

DS25

230Vac 50/60Hz

12

5.4

3.89

16.95

AWG10

25

RS25

230Vac 50/60Hz

12

5.4

3.89

16.95

AWG10

25

3.6

Control wiring

Elite Steam allows connection of any simple or automatic humidistat, and safety

devices such as high-limit humidistat, air flow proving switch, and remote on/off.

The humidifier is operated by the closing of a mechanical humidistat H, or by the

closing of a voltage-free remote contact, or alternatively by a combination of both. The

most common is a combination of a humidistat and pressure switch. The diagrams

in the figures show the connections to be made on the terminal block, in case of:

Fig. 3.u Operation performed by a simple enabling contact;

Fig. 3.t Operation controlled by an external mechanical humidistat;

Fig. 3.v A combination of both humidistat and pressure switch (most common).

Contact AB-AB:

• closed: humidifier enabled to produce steam (production starts when humidistat

closes);

• open: steam production is immediately stopped.

The remote on/off contact is usually a series of external potential-free contacts that

enable the humidifier to produce steam when all of them are closed, indicating the

duct/AHU is ready to accept steam. Connect the 12500 Pressure

Switch NO and C terminals to the AB-AB contacts.

For example,

• fan contact closes when fan is running;

• downstream cooling coil contact closes when coil is off;

• etc.

Contact IN-GND:

• closed: steam production starts if contact AB-AB is closed

• open: steam production is stopped after 5 sec.

Fig. 3.o

Fig. 3.p

Fig. 3.q

L1 L2

Fig. 3.r

Fig. 3.s

Fig. 3.t

Fig. 3.u

Fig. 3.v

DS35

230Vac 50/60Hz

12

5.4

3.89

16.95

AWG10

25

RS35

230Vac 50/60Hz

12

5.4

3.89

16.95

AWG10

25