Elite Steam +030222075 Rev. 3.5 – July 2012

20

5.5

Using the GFX3 Humidistat

Press to select

OFF, MANUAL or AUTO mode (if outdoor sensor is connected).

OFF mode: The humidifier is turned off.

MANUAL mode: The GFX3 will work to maintain the single humidity selected. You can set

your desired humidity level by pressing

or . The humidifier will turn ON or OFF

according to your manual setting. (The humidifier will operate when the measured relative

humidity falls more than 2% below the set point.) Humidity will have to be lowered when

weather is colder or if condensation is suspected.

AUTO mode: The GFX3 will automatically raise the humidity as the outdoor temperature

increases. This provides the highest possible humidity. The GFX3 will automatically lower the humidity as temperatures drop. This

minimizes the risk of condensation on cold surfaces like windows. You can adjust the Auto Humidity Index Set Point from 0 (low) to

10 (high) by pressing

or . The Humidity Index is based on the outdoor temperature and indoor humidity. The humidifier will

switch ON/OFF according to the calculated auto humidity index set point. Lower Index settings are for older homes with less

insulation and vapor barriers. Higher Index settings are for newer homes with complete vapor barriers, triple pane windows and high

R value insulation. If condensation occurs reduce Index setting by 2 points until condensation stops.

NOTE If the outdoor temperature sensor fails, flashes and the unit will default to MANUAL mode.
To toggle between indoor / outdoor temperature and indoor humidity:
Press .

To change the temperature unit: Press °C / °F.

To set the temperature / humidity offset in MANUAL or AUTO mode:

1. Simultaneously press

and when viewing the temperature or humidity reading.

2. Use

or to change the setting (-3 to 3).

3. Press

and simultaneously or wait 5 seconds to confirm and move onto the next setting.

WARNING: Do not allow excess humidification. Excess humidity can cause condensation and enable mold and mildew growth.

5.6

Alarms

In the event of an alarm, the red alarm LED will flash, the alarm relay will close, and the alarm code will flash in the display. Multiple

alarms will flash in sequence, alternating with the main display. Pressing the sel button for 2 seconds will reset the alarms, although

still active alarms will continue to display.

Dis

play

Description

Action

Red

Led

Alarm

Relay

Notes

--

Remote on-off open

Unit disabled

Off

Off

EE

Internal memory error

Unit disabled

On

On

E0

Control board configuration not valid

Unit disabled

On

On

Turn off, check control board, reprogram

E1

High current alarm

Unit disabled

On

On

Turn off, check connections, check

cylinder (no limescale bridges between

electrodes, no electrodes short-circuited)

E2

Low production, low supply water

conductivity or excessive

foam/limescale in the cylinder

Unit disabled.

Press “

reset/sel” key for 1 seconds to reset.

On

On

Check supply water conductivity (too

low?), replace the cylinder.

E3

Cylinder almost exhausted, already

used for 2000 hrs

Press “reset/sel” key for 1 seconds to reset.

Off

Off

Change cylinder (not urgent)

E4

Fill alarm, unable or slow fill

(current does not increase within

timeout)

Press “

reset/sel” key for 1 seconds to reset, otherwise

the warning will be reset automatically every 10

minutes until the supply water is available again.

On

On

Check water supply and fill valve; check

drain pump for leakage

E5

Drain alarm, unable to drain

(current does not decrease within

timeout)

Press “

reset/sel” key for 1 seconds to reset

On

On

Check drain pump and drain connection

E6

Cylinder exhausted

(critical performance detected)

The warning is automatically reset if Elite Steam can

produce the demand, otherwise turn off and then on.

Off

Off

Change cylinder (urgent)

E7

Foam detected

Press “

reset/sel” key for 1 seconds to reset

Off

Off

If it continues, do some cleaning cycles

(read chap. “Starting with a new

cylinder”)

E8

Cylinder lifetime expired (3000 hours)

Unit disabled: Reset the hour counter (read chap.

Resetting the hour counter”)

On

On

Change the cylinder if necessary

E9

High controller temperature (above

176 °F / 80 °C)

The warning is automatically reset if the temperature

decreases below 176 °F / 80 °C.

Off

Off

Check the ambient temperature, replace

the controller.

Suggested

Setting

Outdoor

Temperatures

15%

-20˚F -29˚C

20%

-10˚F -23˚C

25%

0˚F -18˚C

30%

+10˚F -12˚C

35%

+20˚F - 7˚C

40%

+30˚F - 1˚C