Technical specifications – GeneralAire EDMK4 Elite Steam User Manual

Page 24

Advertising
background image

Elite Steam +030222075 Rev. 3.5 – July 2012

24

8. TECHNICAL SPECIFICATIONS

Steam flows, VAC, kW

5.5 lbs/hr (2.5 kg/h): 110 VAC 1-phase 50-60 Hz, 1.86 kW

12 lbs/hr (5.4 kg/h): 230 VAC 1-phase 50-60 Hz, 4.05 kW

Notes

Steam pressure

3.81 in WC / 950 Pa

For duct only

Dimensions (mm )

24” x 14” x 8” (600 x 341 x 204 mm)

(Height x Width x Depth)

Weight empty/packaged/installed

with water

18/22/26 lbs. (8/10/12 kg)

IP class

IP20

Electrode power cables

12 AWG

Power relays

2 x 30 Amp

on board

Ground connection

Screw

Input water type

Potable water

no demin. or softened water

Conductivity range

125-1250 µS/cm

Special cylinders for cond. < 350

Water fill connection

1/4” O.D. Compression

Adapter to ¾” FPS

Water fill - instant flow

0.09 – 0.16 gpm

(0.35 – 0.60 l/min)

Drain connection

32 mm O.D. (1.25”)

Adjustable from horizontal to

vertical.

May be from back or bottom of

unit.

Drain water temp

< 140°F

(< 60°C)

drain tempering device

Drain flow

Initial Max drain rate - 7 gpm (26.2 l/min) (w/ full cylinder –

for the first 10-15 seconds of drain cycle)

Average drain rate – 3.1 gpm (11.7 l/min) (measured over a

one minute period starting with full cylinder)

Embedded fan flow

71 cfm

(120 m³/hr)

Direct Room Discharge Only

Serial communication

RS485

Advertising