3.6.1 Connect the GFX3 Humidistat for On/Off Operation:

1. Remove the humidistat from the base, squeeze the louvered base at the top and bottom. To remove the humidistat from

the wall, lift up on the humidistat and pivot top away from wall.

2. Before wall mounting, please remove the black foam gasket.

3. Before return air duct mounting, please remove the breakout piece.

4. If return air duct mounting, route wires between humidistat and base.

5. Mount the sensor outside the house. Do not mount on South side of the house or in direct sunlight. Place at least 4 feet

away from any exhaust vent. If in air intake, place 1 foot or closer to outside wall. Place at least 6” higher than possible

snow. Do not route sensor wire near high voltage wires.

6. Connect the GND-IN terminals on the humidifier to the HUM terminals on the GFX3 Humidistat. Connect the GND-24V

terminals to the ACL-ACN terminals on the GFX3 Humidistat. see Fig.3.x

3.6.2 Modulating Operation

Connect an external 0...10 Vdc modulating input between terminals IN-GND. Connect any

Safety Switches (high-limit, air flow switch, remote on/off) in series to terminals AB-AB. If

no safety switches are used, then a jumper must be installed between AB-AB. DO NOT

apply any voltage to AB-AB.

3.6.3 Connect the GFX50 humidistat for Modulating Operation

To select signal modulating see Fig 3.y Connect the power supply to the

GFX50 G and G

O terminals, using the terminal GND and 24V on the Elite Steam.

Note MODULATING

OPERATION requires a change in signal type. See SEC. 5.1.1 page 19.

Connect an external signal to the

GFX50 using the terminal IN from the Elite Steam and

AOUT in

GFX50.

See the diagram below.

GFX3 HUMIDISTAT

GFX50 HUMIDISTAT

AIR CONDITIONER RELAY INTERLOCK

N2

GND
N1
AB
AB
GND
IN

NO

C

NC

C
NO

GND
24V

AC
L

AC
N

HUM

SN
SR

OUTDOOR TEMP. SENSOR

(not used in manual mode)

Elite Steam

O

N

D

IP

1

2

3

4

ADCD

DIP SWITCH SETTNGS

FOR HUMIDISTAT ONLY OPER ATION

ON

OFF
OFF

ON

3.6.4 Safety and High Limit Switches

Remove the jumper between terminals AB-AB and connect any simple high-limits, air flow switch, 12500 pressure switch, and

remote contacts in series to terminals AB-AB; otherwise, if no such dry contacts are available, the jumper must remain in place

between terminals AB-AB. DO NOT apply any voltage to AB-AB.

Thread the control wiring through the bottom of the unit, and the strain relief (see photo at top of previous page), and then up the

side of the control module to the top right wiring terminal blocks. Connect the control wiring to the control wiring terminal blocks

found at the top right side of the control module.

3.6.5 Air Conditioner Relay Interlock

Auxiliary DPDT safety relay: Use this method in the following situations:

1. To prevent the air conditioner from running when there is a call from humidity. The DPDT relay will open the “Y” circuit and close

the “G” circuit for operation while a call for humidity is present. Demand for humidity will override call for cooling.

2. In systems using a thermostat where G and Y are a single circuit. The DPDT relay will allow blower operation to occur without

back-feeding the compressor.

Do not use this method when simultaneous humidification and cooling will be desired. Use a high limit humidistat in to avoid

condensation in ductwork.

The humidistat should be set to OFF during the air conditioning season if humidification is not desired.

For variable speed or DC systems, consult furnace manufacturer

.