Installation guide, Balancing the unit, Tips – GeneralAire ERV 3220 User Manual

Page 14: Using the selector switch

Advertising
background image

INSTALLATION

GUIDE

TIPS

to installer
As mentioned in the section, the
Duotrol

TM

System has two different

purposes.

1. Mode Selector
2. Balancing Mode

The light indicator shows you in which
mode the Duotrol

TM

System is in.

GREEN LIGHT

Mode Selector

YELLOW LIGHT

Balancing Mode

Using the
Selector Switch

to installer

When on Balancing Mode, the Selector
Switch allows you to choose the motor
you want to set.

Closed Duotrol Cover

1. INTER (Exhaust Motor)
2. CONT (Both Motors)
3. OFF (Supply Motor)

or

Open Duotrol Cover

1. UP (Exhaust Motor)
2. MIDDLE (Both Motors)
3. DOWN (Supply Motor)

13. Balancing the unit

Step 1: Press the (+) and (–) buttons simultaneously until you
see the yellow light. Once the indicator light turns yellow you
are in balancing mode.

Step 2: When in balancing mode the selector switch becomes
the motor selector switch. INTER (Right Motor), CONT (Both
Motors) and OFF (Left Motor)

Step 3: Once the total cfm needed is determined, you can
start balancing the HRV/ERV. Set your fresh air supply by
selecting the “OFF” position on the Duotrol

TM

. Install your

magnehelic gauge and air flow grid in the fresh air duct.

Step 4: Press the (–) button to decrease the cfm or press the
(+) button to increase the CFM.

Step 5: Then perform the same operation on the stale air side
by selecting the “INTER” position on the Duotrol

TM

.

Step 6: The “CONT” position will allow you to adjust the cfm
on both motors proportionately (if necessary).

Step 7: Once this is completed, you have set the high speed
on your HRV/ERV. To lock balancing mode you must press (+)
and (–) buttons simultaneously and release. The indicator light
will turn green to indicate normal operation mode.

Step 8: Once high speed is set and locked, switch to
continuous on the Duotrol

TM

. By using (+) and (-) buttons set

low speed on the HRV/ERV.

Step 9: Select the mode of operation.
(Intermittent, Recirculation or Continuous Ventilation)

figure 13.1 Duotrol

TM

System

figure 13.2 Magnehelic Gauge with Air Flow Grid

figure 15.6 Selector Switch

figure 13.3 Magnehelic Gauge with Air Flow Grid

figure 13.4 Inserting Air flow grid in duct

figure 13.5 Seal Air flow grid in duct with duct tape.

14

Advertising