Types of installation (continued), Exhaust and supply in the return, Exhaust from the return and supply in supply – GeneralAire ERV 3220 User Manual

Page 5: Simplified connection, Exhaust from return and supply in supply

Advertising
background image

5

Exhaust and
supply in the return

installation

When using this

application make sure

that there is at least

6' between the fresh

air and exhaust air

connections of the

HRV or ERV in the return

air duct.

Supply air from HRV or ERV must be at
least 3' from the forced air system. Can
be different from a region to an other.
You should check with your local code
or the forced air system’s
manufacturer.

Note

to installer

Fresh air must always be down-stream
from the exhaust air in the return air
duct of the forced air system.

Exhaust from the return
and supply in supply

installation

When using this application make sure
that the Supply air from HRV or ERV is
at least 3' from the forced air system.
Can be different from a region to an
other. You should check with your local
code or the forced air system’s
manufacturer.

2. Types of installation (continued)

Simplified Connection

Forced Air System

6’

18”

HRV / ERV

6’

3’

Exhaust and supply in the return

Forced Air System

6’

18”

HRV / ERV

Exhaust from return and supply in supply

FOR MINIMUM DISTANCE BETWEEN
RETURN AND FORCED AIR SYSTEM

Check with your local building codes and force air system manufacturer.