Appendix D Modbus Register Information

Table 2 Sensor Modbus Registers

Tag Name

Register # Data Type Length

R/W

Description

Main Measurement Parameter in
mg/L

40001

Float

2

R

Concentration Measurement Tag in
mg/L

pH Measurement Param.

40003

Float

2

R

pH Measurement Tag

Temperature measurement

40005

Float

2

R

Temperature measurement

Current Measurement Parameter in
µA

40007

Float

2

R

Current measurement in µA

Main Measurement Parameter in
ppm

40009

Float

2

R

Concentration Measurement Tag in
ppm

Main Measurement Parameter in ppb

40011

Float

2

R

Concentration Measurement Tag in
ppb

Main Measurement Parameter
in µg/L

40013

Float

2

R

Concentration Measurement Tag in
µg/L

Current Measurement Parameter in
nA

40015

Float

2

R

Current measurement in nA

Raw pH measurement

40017

Float

2

R

Raw pH measurement

mV Raw measurement

40019

Float

2

R

Raw ORP measurement

Raw Temperature measurement

40021

Float

2

R

Raw Temperature measurement

AutoRange Concentration in ppX

40023

Integer

1

R

Auto Ranging Tag in ppX

AutoRange Concentration in Xg/L

40024

Integer

1

R

Auto Ranging Tag in xg/L

AutoRange Current

40025

Integer

1

R

Auto Ranging redirection of nA-µA
units

Concentration Tag-based

40026

Integer

1

R

Redirection tag for concentration
ppm-mg/L units

Temperature Tag-based

40027

Integer

1

R/W

Redirection tag for temperature unit
(°C-°F)

Sensor Name[0]

40028

Integer

1

R/W

Sensor Name[0]

Sensor Name[1]

40029

Integer

1

R/W

Sensor Name[1]

Sensor Name[2]

40030

Integer

1

R/W

Sensor Name[2]

Sensor Name[3]

40031

Integer

1

R/W

Sensor Name[3]

Sensor Name[4]

40032

Integer

1

R/W

Sensor Name[4]

Sensor Name[5]

40033

Integer

1

R/W

Sensor Name[5]

Function code

40034

Integer

1

Function code

Next Step

40035

Integer

1

Next Step

Password

40036

Pass

1

R/W

Password

Serial Number[0]

40037

Integer

1

R/W

Serial Number[0]

Serial Number[1]

40038

Integer

1

R/W

Serial Number[1]

Serial Number[2]

40039

Integer

1

R/W

Serial Number[2]

Application toogle

40040

Integer

1

R/W

9184..9187 applications

Active Concentration unit

40041

Integer

1

R/W

Active concentration unit (ppm or
mg/L)

Concentration unit toogle

40042

Bit

1

R/W

Concentration unit toogle (ppm-mg/L)

Temperature unit toogle

40043

Bit

1

R/W

Temperature unit toogle (°C-°F)

Concentration offset unit

40044

Integer

1

R

Concentration offset unit (na-µA)

Compensation pH toogle

40045

Integer

1

R/W

Compensation pH toogle
(manual-auto)

pH display format toogle

40046

Bit

1

R/W

pH display format XX.X or XX.XX