3 - 35

Run has the third highest operating priority. Run ramps to the scaled setpoint speed,
using the Acceleration Time (CP-16). Run can be activated when the ML-Drive is in
R–Stop or F–Stop, however Run cannot be activated when the ML-Drive is in Jog.

To activate Run:

• Short the F–Stop and R–Stop inputs to common.
• Open the Jog input.
• Short the Run input to common. (Run is latched and does not need to be

maintained to remain active.)

R-STOP

F-STOP

RUN

JOG

COMMON

R-STOP

F-STOP

COMMON

JOG

RUN

Close Momentarily