Logic Output

The Drive Enable output is controlled by the Ramped Reference (MP-46) and the
feedback. Drive Enable Logic (CP-74) determines which conditions of the Ramped
Reference (MP-46) and feedback will control the Drive Enable output. The Ramped
Reference (MP-46) is the calculated setpoint that is output from the Acceleration/
Deceleration routine.

The factory default for Drive Enable Logic (CP-74) is found in Table 3-27. To modify
this default parameter, refer to Table 3-28. If you are uncertain how to enter a Control
Parameter, review the

Operations: Keypad

section, page 3-3.

Table 3-27 Default Drive Enable Logic Control Parameter

CP

Parameter Name

Parameter Value

CP-74

Drive Enable Logic

0

Table 3-28 Entering Drive Enable Logic Control Parameter

CP

Parameter Name

Parameter Value

CP-74

Drive Enable Logic

Enter “0” in CP-74 to deactivate the Drive Enable
output (output high) when the Ramped Reference is
zero, and activate the Drive Enable output (output low)
when the Ramped Reference is not zero.

Enter “1” in CP-74 to deactivate the Drive Enable
output when both the Ramped Reference and the
feedback are zero, and activate the Drive Enable
output when the Ramped Reference is not zero.