SECTION 3 – ADJUSTMENTS

The switch settings and adjustments in this chapter should be made after your installation and wiring
to the operator(s) is complete. Whenever any of the programming switches on the circuit board are
changed, power must be shut-off, and then turned back on for the new setting to take effect.

• Set the DIP-switches on the circuit board to the desired setting. See switch-setting charts in

section 3.2.

• Auto close timer (when turned on) can be set from 1 second (full counter clockwise) to

approximately 23 seconds (full clockwise).

• Dry contact relay contacts (terminals 16-17) can be set for Normally Open (NO) or Normally

Closed (NC) operation by placing the relay shorting bar on the NO or NC pins respectively.

• Power LED indicates that low voltage power is applied to the circuit board. Input LEDs

should be OFF and will only illuminate when an input is activated. The pulse LEDs will blink
as the operator is running. They can be either ON or OFF when the operator is stopped.
Tracker LEDs will flash as operator data is sent to the access controller (1803PC, 1815, 1817
or 1818).

3.1 CIRCUIT

BOARD

ADJUSTMENTS

GROUND LUG

SLAVE OPERATOR
MOTOR TERMINALS

OPEN
Loop Port

REVERSE
Loop Port

TIMER

Adjust

POWER LED

INPUT LEDs

PULSE LEDs

SW 1

SW 2

TRACKER

LEDs

AUXILIARY TERMINALS 1-8

RELAY SHORTING BAR

Figure 35