PRE-WIRED LOOP INSTALLATION

ON

SL-150

Model

SL-150

IMPORTANT:

provides two pre-wired loop harnesses one for SAFETY LOOP and one for EXIT

LOOP. Loop detectors must be 120 VAC.

To install loop detectors make sure power is off in main power source then simply plug detector
in designated harness socket and wire the ground loop to the grey and brown wires located
inside the electrical box behind operator gearbox. There is one pair labeled EXIT for EXIT LOOP
and one pair labeled SAFETY for SAFETY LOOP.

Use different frequencies for every loop detector.

IMPORTANT: When useing the safety loop, you must remove the jumper from “SAF LOOP” on
terminal strip.

OFF

SAFETY

EXIT

115VAC

LIMIT SWITCHES

EXIT

SAFETY

EXIT LOOP

SAFETY LOOP

Power

Detect

Detect

Loop Fail

Loop Fail

Reset

Reset

2

1

0

0

SENS.
LEVEL

LEVEL

BOOST ON

BOOST ON

PULSE

PULSE

FREQ.

0

0

OFF

PRES

2

1

1

2

3

4

5

6

Power

Detect

Detect

Loop Fail

Loop Fail

Reset

Reset

2

1

0

0

SENS.
LEVEL

LEVEL

BOOST ON

BOOST ON

PULSE

PULSE

FREQ.

0

0

OFF

PRES

2

1

1

2

3

4

5

6

Look for wires
labeled EXIT
in the electrical box

Look for wires
labeled SAFETY
in the electrical box

Twisted wires must be 6 turns per
foot

MINIMUM

Loop harness
Sockets

33

Advertising
This manual is related to the following products: