Alliance Laundry Systems HF150 User Manual

Page 28

Advertising
background image

4

28

Use wire sizes indicated in Table 3 through 6 for runs up to 50 feet.

Use next larger size for runs of 50 to 100 feet. Use two sizes larger for runs greater than 100 feet.

For personal safety and proper operation, the washer-extractor must be grounded in accordance

with state and local standards. If such standards are not available, grounding must conform to

the National Electric Code, article 250. The ground connection must be made to a proven earth

ground, not to a water pipe, gas pipe, or another metal pipe. Provide the necessary equipotential

connections according to the local electrical prescriptions.

GROUNDING INSTRUCTIONS
This appliance must be connected to a grounded metal, permanent wiring system; or an equipment-

grounding conductor must be run with the circuit conductors and connected to the equipment-

grounding terminal or lead on the appliance.

IMPORTANT: Alliance Laundry Systems Warranty does not cover components that fail as a

result of improper input voltage.

Advertising
This manual is related to the following products: