WARNING

The washer-extractor should be connected to an individual branch

circuit not shared with lighting or other equipment.

Electrical Specifications HF234, IHF234, IHF055, CHF234, CHF055

234 liters / 55 pounds

Boiler Fed/Steam Heat

Electric Heat

Code

Voltage

Cycle

Phase

Wire

Full Load

Amps

Recommended Circuit

Breaker (US-market)

AWG/mm2

kW Standard

Heating Elements

Full Load

Amps

Recommended

Circuit Breaker (US-

market)

AWG/mm2

US NON-US

US NON-US

N

440-480 50/60

3

3+PE

8

15

10

14/2.5

6x3 kW

34

40

40

8/10.0

P

380-415 50/60

3

3+N+PE 25

30

30

10/6.0

51

60

60

6/16.0

Q

200-240 50/60

3

3+PE

25

30

30

10/6.0

70

80

80

4/25.0

X

200-240 50/60

1/3

2/3+PE

25

30

30

10/6.0

N/A N/A

N/A

N/A

Alternative Electric Heat Options

N

440-480 50/60

3

3+PE

6x2 kW

25

30

32

10/6.0

P

380-415 50/60

3

3+N+PE

42

50

50

8/10.0

Q

200-240 50/60

3

3+PE

55

60

60

6/16.0

X

200-240 50/60

1/3

2/3+PE

N/A N/A

N/A

N/A

N

440-480 50/60

3

3+PE

3x3 kW +

3x2 kW

29

40

40

8/10.0

P

380-415 50/60

3

3+N+PE

47

50

50

8/10.0

Q

200-240 50/60

3

3+PE

63

70

70

4/25.0

X

200-240 50/60

1/3

2/3+PE

N/A N/A

N/A

N/A

N

440-480 50/60

3

3+PE

3x3 kW +

3x4 kW

38

50

50

8/10.0

P

380-415 50/60

3

3+N+PE

55

60

60

6/16.0

Q

200-240 50/60

3

3+PE

N/A N/A

N/A

N/A

X

200-240 50/60

1/3

2/3+PE

N/A N/A

N/A

N/A

N

440-480 50/60

3

3+PE

6x4 kW

42

50

50

8/10.0

P

380-415 50/60

3

3+N+PE

60

70

70

4/25.0

Q

200-240 50/60

3

3+PE

N/A N/A

N/A

N/A

X

200-240 50/60

1/3

2/3+PE

N/A N/A

N/A

N/A

Table 5