121-000-350 © 2001 Max Machinery, Inc.

ENTER

ENTER

STOP

ENTER

STOP

Calibration
Submenu Group

8.2.6
Calibrate CH1 0mA
Submenu Group

8.2.7
Calibrate CH1 20mA
Submenu Group

Calibrate

Calibrate ch1 0mA
Iin=TB1-3 GND=TB1-4

Calibrate ch1 0mA
CALIBRATING ——

Calibrate ch1 0mA

*** DONE ***

Calibrate ch1 0mA
Iin=TB1-3 GND=TB1-4

Calibrate ch1 20mA
Iin=TB1-3 GND=TB1-4

Calibrate ch1 20mA

0 CALIBRATING ——

Calibrate ch1 20mA

*** DONE ***

Calibrate ch1 20mA
Iin=TB1-3 GND=TB1-4

Advance to

Calibrate ch2 0mA

Press Enter to begin the calibration routine. (Please note the
caution above)

Connect Current Source (+) TB1-3, (-) TB1-4. Input 0mA and
press Enter.

This message is displayed during calibration.

This message is displayed when the 0mA calibration is fin-
ished.

The display will automatically return to the Calibrate CH1
0mA submenu. Press the Down arrow key to advance to the
CH1 20mA calibration.

Connect Current Source (+) TB1-3, (-) TB1-4. Input 20mA
and press Enter.

This message is displayed during calibration.

This message is displayed when the 20mA calibration is fin-
ished.

The display will automatically return to the Calibrate CH1
20mA submenu. Press the Down arrow key to advance to
the CH2 0mA calibration.

ALL I/O REFERNCES ARE CALIBRATED AT THE FACTORY PRIOR TO SHIP-
MENT CAUTION:

This unit must be calibrated using precision and calibrated equipment.
Equipment needed is as follows: Frequency Generator, Digital Multimeter,
Precision Current/Voltage Source, Oscilloscope, Frequency Counter.