Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller Installation User Manual

Page 38

Advertising
background image

3.2.5 CONFIGURE A MODULE

The navigational sequence would be the following:

•

Select Module Type (then Module, if there’s more than one Module)

•

Select Page (Skipped when there’s only a single page)

•

Select Parameter

3.2.5.1 Module-Mode ConfigurationProcedure

•

Press the Mode button to enter ENGINEER mode
indicated by the appearance of either CONFIGURE,
DISPLAY or PROGRAM at the bottom of the display..

•

If CONFIGURE does not appear, press F2 until CON-
FIGURE
appears at the bottom of the display.

•

When CONFIGURE is displayed, press F3 to enter the
CONFIGURE mode.

•

For a Hi-Res display, as shown, press F2 until MOD-
ULE
appears at the bottom of the display.

•

When MODULE is displayed, press F3 to enter the
MODULE mode.

•

The screen should now appear as shown on the right.

•

Select the desired MODULE type to be configured by
using the keys to navigate to the desired mod-
ule type.

•

In this example, the button was used to navigate to
the CONTROL module type as shown to the right.

•

Press F3 to select this Module type.

MODULAR CONTROLLER QUICK START

3-13