RS-485 COMMUNICATIONS SETUP
Table 1. RS-485 Setup Menu
Middle
Display
Bottom
Display
Entry Description
MODE VAL
XXX
Where X = any value between 0 and 255.
This value is OR'd into bits 9-12 of the Control
Mode register (#14) when the activity timer is
enabled. Default value is 1.
MNEMONIC
XXX
Where X = any of the following characters:
Letters A through Z,
Any of the special characters:
b, c, super c, d, h, sub L, super L,
super m, super n, o, r, super T, u,
super V, w, <, >, =, +, –, *, #, /, %,
degrees (super o), or space,
Numbers 0 through
Mnemonic appears in the set-point status
display when the activity timer is initialized by
the host and set-point source is local, or when
coil #8 is True and the computer set-point
mode is Local. Default is LOC.
MNEMONIC
XXX
Where X = any of the characters listed in
Step 8.5.
Mnemonic appears in the set-point status
display when the activity timer is initialized by
the host and set-point source is Local 2.
Default is LO2.
MNEMONIC
XXX
Where X = any of the characters listed in
Step 8.5.
Mnemonic appears in the set-point status
display when the activity timer is initialized by
the host and set-point source is Local 3.
Default is LO3.