Micromod MOD: Modcell 2050R MODBUS Communications User Manual
Page 47

IB-23C650M
CONTROLLER ATTRIBUTE LISTING - REGISTER DATA
Ramp/Soak Profile and Totalizer Data (registers) Cont’d
Reg.
#
Description
Register Value
2050R
Displayed Value
39
R W
Floating point totalizer predetermined
count hi bytes. Upper 2 bytes of
totalizer predetermined count in IEEE
floating point format.
Same as Reg #33
Same as Reg #33
40
R W
Floating point totalizer predetermined
count low bytes. Lower 2 bytes of
predetermined count in IEEE floating
point format
Same as Reg #33
Same as Reg #33
41
R W
Integer totalizer predetermined count.
Permits transfer of totalizer
predetermined count in integer format.
Same as Reg #35
Same as Reg #35
42
R _
Totalizer scale decimal point. Sets the
decimal point position in the totalizer
scale factor (Reg. # 43).
0
1
2
3
0
0.0
0.00
0.000
43
R W
Totalizer scale factor. Permits
fractional scaling of an input signal.
Register No. 42 =0
Register No. 42 =1
Register No. 42 =2
Register No. 42 =3
1 to 30000
1 to 30000
1 to 30000
1 to 30000
1 to 30000
0.1 to 3000.0
0.01 to 300.00
0.001 to 30.000
43