CONTROLLER ATTRIBUTE LISTING - REGISTER DATA
Computer Activity Data (registers) Cont’d
Reg.
#
Description
Register Value
2050R
Displayed Value
80
R W
Computer active: set-point mode value
0 to 255
0 to 255
81
R W
Computer fail: control mode
0
1
2
Last
Manual
Auto
82
R W
Computer fail: output value
0 to 1000
0.0 to 100.0%
83
R W
Computer fail: output 2 value
0 to 1000
0.0 to 100.0%
84
R W
Computer fail: relay A
0
1
2
Last
Off
On
85
R W
Computer fail, relay B
Same as Reg. #84
Same as Reg. #84
86
R W
Computer fail: relay C
Same as Reg. #84
Same as Reg. #84
87
R W
Computer fail: set-point mode
0
1
2
3
4
5
Last
LOC
LO2
LO3
LO4
REM
88
R W
Computer fail: set-point value
Register #9, bits 1 & 0 = 0
Register #9, bits 1 & 0 = 1
Register #9, bits 1 & 0 = 2
Register #9, bits 1 & 0 = 3
-3000 to 30000
-3000 to 30000
-3000 to 30000
-3000 to 30000
-3000 to 30000
-300.0 to 3000.0
-30.00 to 300.00
-3.000 to 30.000
See register #113 through #131 for
more computer activity data