MODBUS PROTOCOL
Message Formats
The following message formats are used to transfer information between the
controller and a host. Refer to the message format example for format details.
Read Coil Status, Read Input Status
Master Message Format Bytes
0
1
2 & 3
4 & 5
6 & 7
Device Address Function Code
Starting Coil Number
Number of Coils
CRC
Slave Response Bytes
0
1
2
3
...
x
x+1 &
x+2
Device
Address
Function
Code
Number of
Data Bytes
Data byte #1
... Data Byte #n
CRC
Read Holding Registers, Read Input Registers
Master Message Format Bytes
0
1
2 & 3
4 & 5
6 & 7
Device Address Function Code
Starting Register Number Number of Registers CRC
Slave Response Bytes
0
1
2
3 & 4
...
x & x+1
x+2 &
x+3
Device
Address
Function
Code
Number of
Data Bytes
Register #1
data
... Register #n
data
CRC
Force Single Coil
Master Message Format Bytes
0
1
2 & 3
4 & 5
6 & 7
Device Address Function Code
Coil Number
Coil Data
ON = FF00
OFF =0000
CRC
Slave Response (simple echo) Bytes
0
1
2 & 3
4 & 5
6 & 7
Device Address Function Code
Coil Number
Coil Data
ON = FF00
OFF =0000
CRC