Output Holder Instructions

CONFIGURATION

Figure 4 .12. Execution Order

8. Optionally you can also include the feedback (RETURN) only in the configuration and not

the presence of the output holder (SENSE). In this case you do not need the discrete
input module in the controller. The configuration will not have the SENSE (DIM),
SENSEF (DI) and the OP_T_LGC (EX) blocks. You can delete these blocks from the
loaded compound. You would still need to connect a track command input to the PID
block. This will again be the RUNINIT signal from the IF block connected to the TCI
attribute of the PID block ensuring bumpless transfer of the output value. Refer to the
section 4.4 Connection RUNINIT from the IF block, Option 2 for the procedure.


9. Compile and download your database to the controller.