NOTICE

Bypassing any switch is intended for testing purposes only. Do not leave switch bypassed
during normal operation or the heater’s built-in safety mechanisms will be compromised.

Is 120V coming

to the fan?

Check for loose wiring

or resistance in hose

connection to pressure

switch. Are they ok?

The heater is equipped with a safety pressure

switch. This differential switch, located in the controls

compartment, is a normally open pressure switch.

Temporarily place jumpers across the terminals of the

switch. Does the light energize?

15

4.0

Troubleshooting Guide

Key

Start

Question

Process

Question

Corrective

Action

DX3

Series

Yes

No

The fan is faulty

and must be

replaced.

Correct

wiring.

Repair.

No

Yes

Yes

Replace faulty light.

No

Replace the differential switch after verifying the following:

• Baffle(s) is/are in the radiant tube(s) farthest from the burner.

• The heater, fan blower, squirrel cage, intake and exhaust are free from

dirt and obstructions.

• The 4” air intake pipe does not exceed 20 feet and/or 2 elbows.

• There is not a negative pressure experienced at the area of air intake

(i.e., attic space, high winds, very tight building).

If any of the above are occurring, please address the problem.

Is resistance through

the igniter 50-400

?

Replace

igniter.

No

Consult

factory.

Yes

Check to make sure gas

pressure is within minimum

and maximum inputs, as

indicated on burner rating

plate. Is gas pressure OK?

Replace gas valve.

Yes

Correct problem.

No