Were the gas lines purged of air?

Is the heater properly

grounded? Is the heater’s

polarity correct?

With micrometer, check

amperage at flame rod. Is it

greater than 1.0 microamps?

Check to make sure flame

sensor wire is OK. If so,

then replace circuit board.

Sensing rod is faulty or flame

is weak. Check to make sure

heater is operating at proper

gas pressure as indicated on

burner rating plate and then, if

needed, replace sensing rod.

Correct problem.

No

Yes

Yes

No

Purge gas line.

No

4.0

Troubleshooting Guide

DX3

Series

Yes

Confirm manifold pressure is

correct and/or gas orifice is not

plugged and is the correct size.