GROUNDING

Grounding the AeGIS steel enclosure is essential. Please comply with all local ordinances and industry standard
procedures to ensure a complete and safe ground. Recommended earth grounds are:

• Use 18-gauge solid wire for grounding.
• Installing a ground steel rod from the AeGIS steel enclosure to the earth ground.
• Installing a solid heavy gauge wire from the AeGIS steel enclosure to a water pipe.
• Connecting the AeGIS steel enclosure to any earth grounded steel metal.

TELEPHONE LINE

It is recommended to install Surge protector to protect the system from telephone line surge. Pach and Company will not
warranty the system from lightning and power surge. “

DEDICATED TELEPHONE LINE IS REQUIRED FOR EACH SYSTEM

IF SOFTWARE REMOTE PROGRAMMING IS USED”.

“UP TO EIGHT SYSTEMS CAN BE CONNECTED TO SINGLE

PHONE LINE IF SOFTWARE REMOTE PROGRAMMING IS NOT USED”

• Twisted pair category 5 is the minimum requirement if the distance less than 200 feet. Shielded wires are

recommended to avoid radio reception or any other noise problems. If the distance is more than 200 feet,
2-conductors, 18-gauge shielded stranded is recommended. Ground one end of the shielded to earth ground.
See installation instruction if ASP1 Surge Protector is used.

• If a PBX line is used connect the AeGIS to the analog PBX's extension to dial the extensions within the PBX.

Do not connect to a PBX's Digital Port.
NOTE:

The AeGIS 9000 Series only works behind the PBX to dial extensions, no pause can be programmed on

the AeGIS 9000 Series to dial the outside line.

DOOR STRIKE OR ELECTRICAL STRIKE

The AeGIS 9000 Series provides TWO relay form "C" dry contact: Normally Open (NO) and Normally Closed (NC).

• 10 Ampere 120 VAC or
• 10 Ampere 24 VDC or
• 7 Ampere 250 VAC

See figure 2.1 for door strike wiring diagram. You MUST use two conductors 18 gauge stranded wire minimum.

Note:

Some door strikes are creating electrical or magnetic noise or spikes and could create problem to the system's
memory. Although the system's relay has built-in filtration circuit, installing an isolation relay is recommended if the
system is experiencing with looses memory.

POSTAL LOCK

The AeGIS system comes with pre-wired "Normally Open" postal switch as shown on figure 2.2(a). If the postal switch is
pressed, the gate will open. If you need "Normally Closed" postal switch, see figure 2.2(b).
The postal lock is not included. You have to purchase the postal lock from your local post office. See figure 2.2 to alter the
postal switch to normally closed.

1

2

Pach and Company

Chapter 2

Page 5

AeGIS 9000 Series

INSTALLATION

3

4

Figure 2.2 (a)

Figure 2.2 (b)

LCOM

POST

LCOM

POST