120v, 277v – Emergi-Lite Survive-All SV Series User Manual

Page 3

Advertising
background image

SV Series – Survive-All

3/4

Emergi-Lite

Tel: (888) 552-6467

Fax: (800) 316-4515

www.emergi-lite.com

10/13 750.1518 Rev. B

b. Refer to figure 8 for 120VAC input voltage and to figure 9 for

277VAC . Use wire taps provided with the hardware kit to connect
battery heater. Unused wires must be insulated to prevent short-
ing.

c. Re-install the batteries. Battery heater is placed between the bat-

tery and the backplate. See figure 6 for battery

wiring diagram.

Re-install the electronic module as shown on figure 5.

d. Connect transformer harness to AC harness.

7. For unit with remote capacity, connect remote heads to termi-

nal L+ and L- (see figure 11).

Calculation of total allowable remote capacity of unit:
Maximum remote lamp power = unit capacity minus the total power of
lamps included with unit.

8. Snap electronic module on backplate.

9. Adjust lamp aiming.

10.Install the lens by using the 6 tamper-proof screws (1). To

insure water tightness, gasket screws (x6) have to be installed
from the inside (see figure 3). Tighten the screws approxi-
mately 5 Lb.-Ft. DO NOT OVER TIGHTEN.

11. For food processing areas, in order to avoid food accumula-

tion, screw caps have to be installed (provided with the hard-
ware kit).

12.Energize AC. Lamps will turn on for few minutes.

13.See page 4 for testing procedure.