Wall Mount (Single Face Model Only)

a. Remove j-box assembly from carton. Remove j-box cover from j-

box assembly, install Hub on j-box and retain securement screw.

b. Remove the backplate(9) from the packaging. Determine the

proper knockouts to remove for mounting to the junction box (see
fig.3).

c. Support area around knockouts with two blocks of wood. Strike

knockouts from the inside with a hammer and a screwdriver.

d. Reinstall the backplate to the frame using the 6 tamper-proof

screws (use the supplied bit).

2. Electrical connections: Connect one end to the transformer leads,

inside the enclosure, and the other end, to AC line voltage inside the
junction box. Connect the white lead to neutral and the purple lead to
AC line voltage (the input is universal 110 to 347 VAC). (See fig. 4).
Connect the ground(green wire) to the junction box.
Optional: For AC models used with DC remote power. One end con-
nects to the LED-STRIP leads, inside the enclosure, and the other
end to DC input inside the junction box. Connect the red lead to pos-
itive, and the blue lead to the negative of the remote DC input (See
fig. 4).

3. For ceiling mount: Mount the frame and j-box cover assembly to

junction box by using the provided securement screw.
For wall mount: Attach the frame(6) to the junction box, using the
junction box supplied screws.Install 2 stem washers to ensure bond-
ing.

4. Reinstall the diffuser and the EXIT panel (if required, remove the

appropriate chevron).

5. Install the lens by using the 6 tamper-proof screws.

The tamper-proof screws should be equally torqued to approxi-
mately 5 lbs-in (0.6 N-m).

6. Energize AC. Sign will illuminate.

Manual Testing (Self-Powered Models)

Operate the magnetic “test switch” by holding the provided magnet
underneath the unit where indicated on the frame. The AC pilot lamp will
go out, the legend will flicker, but remain lit. Remove the magnet. The
AC pilot light will turn on, the legend will flicker but remain lit.

Automatic Testing (Self-Powered Models)

The unit will perform an automatic self-test of 30 seconds every 30 days,
60 second every 60 days and a 90 minute self-test once a year.