Svxhz series – exit sign, Nexus models, Automatic diagnostics (self-powered models) – Emergi-Lite Survive-All SVX-HZ Series User Manual

Page 3: Maintenance (all models)

Advertising
background image

SVXHZ Series – Exit Sign

3/4

Emergi-Lite

Tel: (888) 552-6467 ext. 547 or 255

Fax: (888) 867-1565

www.emergi-lite.com

06/07 750.1300 Rev. A

Nexus models

Refer to figure 5 for the wiring of Nexus models.
These units can accept an input voltage of 120 or 277 VAC:

120 VAC — Connect the black (120 VAC) lead and white (neutral) lead
to the building utility. Insulate the red wire.

277 VAC — Connect the orange (277 VAC) lead and white (neutral) lead
to the building utility. Insulate the black wire.
Feed excess wire into the junction box.
Leave as much space as possible between the live voltage cabling and
the unsheathed low voltage data cabling.
Run the double insulation of data cables past the line cabling section and
only strip back the last 30mm of the data cable sheathing.

Automatic Diagnostics (Self-Powered Models)

There are three diagnostic indicators: one external and two internal. Unit
must be opened to gain access to internal indicators.
External: General alarm, “Service Required”. The LED will blink if any
alarm condition is detected (see fig. 6).
Internal: Battery Alarm & Charger Alarm. Steady ON if alarm condition
exists (See fig. 7).

Normal operation, No fault — “Service Required” is OFF and one of
the two internal LED blinks, showing that the micro controller is active.

Faulty operation — “Service Required” blinks.
Battery Alarm ON, Charger Alarm OFF: Check battery or replace battery.
Battery Alarm ON, Charger Alarm ON: Check LED strip.
Battery Alarm OFF, Charger Alarm ON: Check charger circuit.

Nexus models

Nexus models use two local indicators. One is a green LED for AC pilot
lamp. The other is a tricolor LED (Service) which identifies and displays
the Nexus status. The table below describes each status:

Nexus Tricolor LED — Status table

Maintenance (All Models)

None required. If AC supply to the unit is to be disconnected for 2
months or more, the battery must be disconnected, Self-Powered Mod-
els only.

Canopy

Figure 5

LED Strip

Nexus data

Black (120)

Red (insulate)

White (neutral)

Black (insulate)

White (neutral)

120 VAC or 277 VAC

Sign

30 mm

Interface

Data

Tape

Nexus data cables

Nexus data

Nexus

Transformer

Nexus model wiring

terminal block

cables

Orange (277)

Figure 6

Figure 7

Battery Alarm

Charger alarm

Diagnostic board

Uncommissioned

Commissioned

Normal

Red/Off pulsing

Green steady

Under test

N/A

Green/Off pulsing

Wink mode

Yellow-orange/(red or off) pulsing

Yellow-orange/Off pulsing

Neuron faulty

Red Steady

Red steady

Power fail

Off

Off

Battery disconnected

N/A

Off