Configuration – APC SMART-UPS SUA3000 User Manual

Page 10

Advertising
background image

10

Smart-UPS XL 3U Rack Mount 2200/3000 VA 120/230 Vac; 3000 VA 100/200 Vac User Manual

Configuration

Configuration

UPS settings

Settings are adjusted through PowerChute software or optional SmartSlot accessory cards.

Function

Factory

Default

User Selectable

Choices

Description

Automatic
Self-Test

On startup and
every 14 days
(336 hours)

there after

• Every 7 days

(168 hours)

• On startup and every

14 days (336 hours)
there after

• On startup only
• No self-test

Set the interval at which the UPS will execute a
self-test.

UPS ID

UPS_IDEN

Up to eight characters
(alphanumeric)

Uniquely identify the UPS, (i.e. server name or
location) for network management purposes.

Date of Last
Battery
Replacement

Manufacture
Date

mm/dd/yy

Reset this date when you replace the battery
module.

Minimum Capacity
Before Return from
Shutdown

0 percent

• 0%
• 15%
• 30%
• 45%

• 60%
• 75%
• 90%

Specify the percentage to which batteries will
be charged following a low battery shutdown
before powering connected equipment.

Voltage Sensitivity
The UPS detects

and reacts to line
voltage distortions
by transferring to

battery operation to
protect the
connected

equipment.

High sensitivity

Brightly
illuminated: high

sensitivity
Dimly illuminated:
medium sensitivity
No illumination:
low sensitivity

Adjust by pressing the Sensitivity switch
located on the rear panel next to the green

Sensitivity LED. Use a pointed object, such as
a pen to do so.
Note: In situations of poor power quality, the

UPS may frequently transfer to battery
operation. If the connected equipment can
operate normally under such conditions, reduce

the sensitivity setting to conserve battery
capacity and service life.
Voltage sensitivity levels can be changed

through PowerChute software.

Alarm Delay
Control

Enable

• Enable
• Mute
• Disable

Mute ongoing alarms or disable all alarms
permanently.

Shutdown Delay

90 seconds

• 0 s
• 90 s
• 180 s
• 270 s

• 360 s
• 450 s
• 540 s
• 630 s

Set the interval between the time when the UPS
receives a shutdown command and actual
shutdown.