APC SMART-UPS SUA3000 User Manual

Page 9

Advertising
background image

Smart-UPS XL 3U Rack Mount 2200/3000 VA 120/230 Vac; 3000 VA 100/200 Vac User Manual

9

Start-up and Operation

Diagnostic Utility
Voltage

The UPS has a diagnostic feature that indicates the utility voltage.
The UPS starts a self-test as part of this procedure. The self-test does not affect

the voltage display.
Press and hold the Test button to view the utility voltage bar graph indicator.
As soon as the On Line LED starts flashing indicating a self-test is in progress,

the five-LED Battery Charge indicator will indicator on the right of the
display panel will show the utility input voltage.
Refer to the figure on the left for the voltage reading.
Values are not listed on the UPS.
The indicator on the UPS shows the voltage is between the displayed value on
the list and the next higher value, (see Troubleshooting in this manual).

Feature

Button

Feature Title

Function

Power On

Press this button to turn on the UPS. Continue reading for additional

capabilities.

Power Off

Press this button to turn off the UPS.

Self-Test

Automatic: The UPS performs a self-test automatically when turned on,
and every two weeks thereafter (by default). During the self-test, the UPS

briefly operates the connected equipment on battery.
The self-test is a diagnostic test of the condition of batteries and connected
equipment.
Manual: Press and hold the TEST

button

for a few seconds to initiate a

self-test.

Cold Start

When there is no utility power and the UPS is off, the cold start feature will
switch the UPS and connected equipment onto battery power,
(see Troubleshooting in this manual).