Configuration

Connect the Emergency Power Off option

The Emergency Power Off (EPO) option is a safety feature that will immediately remove power to all

connected equipment. When the EPO button is pushed, all connected equipment will immediately turn off and

will not switch to battery power.
Adhere to all national and local electrical codes when wiring the EPO.

1. Use the EPO terminal block supplied with the UPS.
2. Insert one wire from the EPO cable into the +24 terminal, and one wire into the IN

terminal of the EPO terminal block.

3. Secure the connection by tightening the screws on the EPO terminal block.
4. Plug the terminal block into the UPS.

The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it only to other SELV circuits.

The EPO interface monitors circuits that have no determined voltage potential. Such closure circuits

may be provided by a switch or relay properly isolated from the utility. To avoid damage to the UPS, do

not connect the EPO interface to any circuit other than a closure type circuit.
Use one of the following cable types to connect the UPS to the EPO switch.

CL2: Class 2 cable for general use.

CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.

CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.

CLEX: Limited use cable for use in dwellings and for use in raceways.

For installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable).

For installation in other countries: Use standard low-voltage cable in accordance with national and

local regulations.

Low Transfer Point

100 V models:
92 Vac

• 86 Vac
• 88 Vac

• 90 Vac
• 92 Vac

To avoid unnecessary use of the battery where
utility voltage is chronically low, set the low

transfer point lower if the connected equipment
can tolerate this condition.

120 V models:
106 Vac

• 97 Vac
• 100 Vac

• 103 Vac
• 106 Vac

200 V models:
184 Vac

• 173 Vac
• 176 Vac

• 180 Vac
• 184 Vac

230 V models:
208 Vac

• 196 Vac
• 200 Vac

• 204 Vac
• 208 Vac

Output Voltage
230 V models

230 Vac

• 220 Vac

• 240 Vac

230 V models only: Sets the UPS output
voltage.

Function

Factory

Default

User Selectable

Choices

Description